Kenco-engineering KPS Bedienungsanleitung

Stöbern Sie online oder laden Sie Bedienungsanleitung nach Sensoren Kenco-engineering KPS herunter. Kenco Engineering KPS User Manual Benutzerhandbuch

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 4
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 0
KENCO ENGINEERING COMPANY
P.O. BOX 470426 TULSA, OK 74147-0426
PHONE(918) 663-4406 FAX: (918) 663-4480
www.kenco-eng.com e-mail:[email protected]
INSTALLATION INSTRUCTIONS FOR MODEL KPS OIL LEVEL SWITCH
WITH ADAPTERS (INCLUDING HIGH PRESSURE MODELS)
Note: For fire safe oil level controllers (KPS-FS) see additional instructions in this work sheet covering installation of fire safe
valves.
PNEUMATIC SWITCH INSTALLATION:
Connect the supply line of air pressure to the ¼” pipe thread located at the top of the air valve (D)
Note: Acceptable air pressure range is 10 psi to 100 psi. Air pressure greater than 100 psi will prevent the switch from operating.
The exhaust vent is located at the base of the air valve (E) and is 1/8” pipe thread.
Note: If an exhaust line is used to carry gas away from the pneumatic switch, this line must be short, undamaged and trap free.
COMMON PROBLEMS AND SOLUTIONS
:
Leaking switch may be caused by dirt. Wash the assembly in solvent to remove any foreign material.
The switch is not tripping. Check for excessive restriction from a long exhaust line, a damaged line or a line with moisture
traps, or excessive pressure from the supply line.
The switch is not properly tripping. Check the pressure coming into the switch. The switch may need adjustment. See below:
PNEUMATIC SWITCH ADJUSTMENT: The switch is factory set at 60 psi with a trip point of 5/8” to ¾” oil drop.
Remove the controller from the housing.
Connect the supply pressure to the pneumatic valve (D).
With the switch float arm against the magnet, adjust screw (C) until there is no leakage from the pneumatic valve.
To adjust for a higher or lower level release lock nut (A) and backing screw (B) out.
For a lower level, turn screw (B) in and readjust screw (C).
Note: Screw (C) must be adjusted until there is no leakage from the valve with the float assembly resting against the magnet.
Figure 1- Pneumatic Switch Adjustment
Seitenansicht 0
1 2 3 4

Inhaltsverzeichnis

Seite 1 - KENCO ENGINEERING COMPANY

KENCO ENGINEERING COMPANY P.O. BOX 470426 TULSA, OK 74147-0426 PHONE(918) 663-4406 FAX: (918) 663-4480 www.kenco-eng.com e-mail:[email protected]

Seite 2 - Figure 3

II. INSTALLATION INSTRUCTIONS FOR UNITS WITH ADAPTERS: OIL LEVEL CONTROLLERS WITH –9 (Universal adapter), -10(Slotted universal adapter), -12 (Pole

Seite 3

OIL LEVEL CONTROLLER WITH –17 (Waukesha VHP Engines F2895, F3251, F5108, L5790 & L7042), -18 (-17 w/ meter), -27 (for newer Waukesha engines same

Seite 4 - V. START-UP PROCEDURES

IV. INSTALLATION INSTRUCTIONS FOR FIRE SAFE VALVES: See Figure 5 MODEL 50-FS AND 75-FS (PATENT NO. 3,877,476) NOTE: All lines between thermal valv

Kommentare zu diesen Handbüchern

Keine Kommentare